Technical Data
4.13 Automatic Reclosing (Optional)
SIPROTEC, 7SD80, Manual
E50417-G1140-C474-A1, Release date 09.2011
317
4.13 Automatic Reclosing (Optional)
Automatic Reclosures
Number of reclosures max. 2
Type (depending on order variant) 3-pole
Control with pickup or trip command
Action times
Initiation possible without pickup and action time
0.01 s to 300.00 s; Increments 0.01 s
Dead times prior to reclosure
separately for all types and all cycles
0.01 s to 1800.00 s; Increments 0.01 s
Dead times after evolving fault recognition 0.01 s to 1800.00 s Increments 0.01 s
Blocking time after reclosure 0.50 s to 300.00 s Increments 0.01 s
Blocking time after dynamic blocking 0.5 s
Blocking time after manual closing 0.50 s to 300.00 s; 0 Increments 0.01 s
Start signal monitoring time 0.01 s to 300.00 s Increments 0.01 s
Circuit breaker monitoring time 0.01 s to 300.00 s Increments 0.01 s