EasyManuals Logo

Siemens SIPROTEC 7SD80 User Manual

Siemens SIPROTEC 7SD80
416 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #168 background imageLoading...
Page #168 background image
Functions
2.14 Monitoring Functions
SIPROTEC, 7SD80, Manual
E50417-G1140-C474-A1, Release date 09.2011
168
A wire break is signaled under the following conditions:
• A suspected local wire break has been detected.
• The logic for detecting the circuit-breaker position (see Section 2.16, Detection of the Circuit-Breaker Posi-
tion) does not signal an open circuit-breaker pole. Broken wire detection is not possible if the circuit breaker
is open. If the breaker position cannot be determined, a closed circuit breaker is assumed.
• The ground current is measured on the additional current transformer I
4
. In this current channel and in all
voltage channels, no jump must have been detected. Jumps in these channels indicate a genuine power
system fault.
• In the other current channels, there must have been no jump without wire break detection. Jumps in the
other current channels also suggest a power system fault, except if a suspected local wire break has been
detected for the affected phases.
• The device at the other end of the protected object must not have signaled a jump. The jump information is
transferred together with the differential protection measurements, so that this information is available simul-
taneously with the first run of the differential protection after the jump.
• In the phase, none of the devices of the protected object may have measured a phase current of more than
2 I
Nom
. A phase current of such a magnitude is a certain indicator of a power system fault.
When a wire break has been detected according to the above criteria, it is signaled via the protection data in-
terface to the device at the other end of the protected object and leads immediately to a wire break message.
The differential protection functions are blocked as well if this has been configured.
In the event of a local wire break, the device generates the indication „Wire break I
X
“ (No. 290, 291, 292).
If a wire break is detected at the other end of the protected object, the indication „Wire break at the other endI
X
“
(No. 297, 298, 299) is generated.
If the broken wire monitoring is disabled, the message 295 „Broken wire OFF“ is output.
The broken wire monitoring is reset by the return of the phase current (I
Lx
> 0.05 I
Nom
) or by the binary input
message 3270 „>RESET BW“. In 1-1/2 circuit-breaker arrangements, the function can only be reset by the
binary input message because the current magnitude is no reliable criterion for a reset of the broken wire mon-
itoring.
If the communication between the devices is disturbed, the device operates in emergency operation. The dif-
ferential protection is not active. The wire-break detection only works with the local available information. Multi-
pole wire break is not reported in emergency operation.
Note that electronic test devices do not simulate the correct behavior of broken wire so that pickup may occur.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SD80 and is the answer not in the manual?

Siemens SIPROTEC 7SD80 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7SD80
CategoryProtection Device
LanguageEnglish

Related product manuals