Functions
2.18 Breaker Control
SIPROTEC, 7SD80, Manual
E50417-G1140-C474-A1, Release date 09.2011
224
The following figure shows the configuration of the interlocking conditions using DIGSI.
Figure 2-88 DIGSI dialog box for setting the interlocking conditions
The configured interlocking causes are displayed on the device display. They are marked by letters explained
in the following table.
Table 2-15 Command types and corresponding messages
Control Logic using CFC
For the bay interlocking a control logic can be structured via the CFC. Via specific release conditions the infor-
mation “released” or “bay interlocked” are available (e.g. object "52 Close" and "52 Open" with the data values:
ON / OFF).
Interlocking Commands Abbrev. Display
Switching Authority L L
System interlocking S A
Zone controlled Z Z
SET = ACTUAL (switch direction check) P P
Protection blocking B B