Appendix
A.8 Settings
SIPROTEC, 7SD80, Manual
E50417-G1140-C474-A1, Release date 09.2011
365
2634 51-B TD IEC Back-Up O/C 0.05 .. 3.00 sec; 0.50 sec 51-B Time Dial for IEC character-
istic
2634 67-TOC TD IEC Back-Up O/C 0.05 .. 3.00 sec; 0.50 sec 67-TOC Time Dial for IEC char-
acteristic
2635 51-B TD ANSI Back-Up O/C 0.50 .. 15.00 ; 5.00 51-B Time Dial for ANSI charac-
teristic
2635 67-TOC TD ANSI Back-Up O/C 0.50 .. 15.00 ; 5.00 67-TOC Time Dial for ANSI char-
acteristic
2636 51-B AddT-DELAY Back-Up O/C 0.00 .. 30.00 sec 5.00 sec 51-B Additional Time Delay
2636 67-TOC AddTDel. Back-Up O/C 0.00 .. 30.00 sec 5.00 sec 67-TOC Additional Time Delay
2637 51-B Inrush Back-Up O/C NO
YES
NO 51-B Inrush blocking
2637 67-TOC Inrush Back-Up O/C NO
YES
NO 67-TOC Inrush blocking
2638 51N-B PICKUP Back-Up O/C 1A 0.05 .. 4.00 A; ∞∞A 51N-B Pickup
5A 0.25 .. 20.00 A; ∞∞A
2638 67N-TOC PICKUP Back-Up O/C 0.05 .. 4.00 A; ∞∞A 67N-TOC Pickup threshold
2639 51N-B TD IEC Back-Up O/C 0.05 .. 3.00 sec; 0.50 sec 51N-B Time Dial for IEC charac-
teristic
2639 67N-TOC TD IEC Back-Up O/C 0.05 .. 3.00 sec; 0.50 sec 67N-TOC Time Dial for IEC char-
acteristic
2640 51N-B TD ANSI Back-Up O/C 0.50 .. 15.00 ; 5.00 51N-B Time Dial for ANSI char-
acteristic
2640 67N-TOC TD ANSI Back-Up O/C 0.50 .. 15.00 ; 5.00 67N-TOC Time Dial for ANSI
char.
2641 51N-B AddTdelay Back-Up O/C 0.00 .. 30.00 sec 0.00 sec 51N-B Additional Time Delay
2641 67N-TOC AddTDel Back-Up O/C 0.00 .. 30.00 sec 0.00 sec 67N-TOC Additional Time Delay
2642 IEC Curve Back-Up O/C Normal Inverse
Very Inverse
Extremely Inv.
LongTimeInverse
Normal Inverse IEC Curve
2642 IEC Curve Back-Up O/C Normal Inverse
Very Inverse
Extremely Inv.
LongTimeInverse
Normal Inverse IEC Curve
2643 ANSI Curve Back-Up O/C Inverse
Short Inverse
Long Inverse
Moderately Inv.
Very Inverse
Extremely Inv.
Definite Inv.
Inverse ANSI Curve
2643 ANSI Curve Back-Up O/C Inverse
Short Inverse
Long Inverse
Moderately Inv.
Very Inverse
Extremely Inv.
Definite Inv.
Inverse ANSI Curve
2644 51(N)-B PilotBI Back-Up O/C NO
YES
NO Instantaneous trip via Pilot
Prot./BI
2644 67(N)TOC Pil/BI Back-Up O/C NO
YES
NO Instantaneous trip via Pilot
Prot./BI
2650 50(N)-STUB OpMo Back-Up O/C ON
Only Emer. prot
OFF
OFF 50(N)-STUB Operating Mode
2651 50-STUB PICKUP Back-Up O/C 1A 0.10 .. 25.00 A; 1.50 A 50-STUB Pickup
5A 0.50 .. 125.00 A; 7.50 A
2652 50-STUB DELAY Back-Up O/C 0.00 .. 30.00 sec; 0.30 sec 50-STUB Delay
2653 50-STUB Inrush Back-Up O/C NO
YES
NO 50-STUB Inrush blocking
2654 50N-STUB PICKUP Back-Up O/C 1A 0.05 .. 25.00 A; 0.20 A 50N-STUB Pickup
5A 0.25 .. 125.00 A; 1.00 A
2655 50N-STUB DELAY Back-Up O/C 0.00 .. 30.00 sec; 2.00 sec 50N-STUB Delay
2656 50STUB Pilot/BI Back-Up O/C NO
YES
NO Instantaneous trip via Pilot
Prot./BI