Channel HW configuration
(fixed when ordering)
SW configuration
available to the user
4 Signal output
Current (0/4-20 mA)
Frequency or pulse
Three-stage analog valve dosing control
Discrete one or two-valve dosing control
Operational and alarm status
Relay output
Discrete one or two-valve dosing control
Operational and alarm status
Signal input
Dosing control
Totalizer reset
Remote zero adjust
Force or freeze output(s)
8.2.6.1 Current output
All four channels can be configured as current output.
Current output configuration
The following process values can be assigned to the current output:
Mass flow
Volume flow
Standard volume flow
Density
Temperature
Fraction A (Volume flow or Mass flow)
Fraction B (Volume flow or Mass flow)
Fraction A %
Fraction B %
Control valve *
The process variable listed above with * is not available to be allocated to the 4 to 20 mA output
on Channel 1. All process variables are available through bus communication (SV, TV and QV
variables) and on all of Channels 2 to 4.
The accuracy specified for the analog output signal applies only within the range 4 to 20 mA.
Lower limit (4 mA) and upper limit (20 mA) can be assigned to any specific flow values.
Parameter assignment
8.2 Functions
SITRANS FC330
Operating Instructions, 01/2019, A5E44030648-AB 135