11.4 Inputs
Table 11-10 Digital input
Description Channels 3 to 4
Load 15 to 30 VDC, R
in
7 kOhm
Functionality
Start/stop/hold/continue dosing
Reset totalizer 1, 2 or 3
Reset all totalizers
Freeze output
11.5 Outputs
Table 11-11 Current output (Channel 1)
Description Channel 1
Signal range 4 to 20 mA
Resolution 0.4 μA
Load
Ex i: <470 Ω (HART ≥ 230 Ω)
Non-Ex: <770 Ω (HART ≥ 230 Ω)
Time constant (adjustable) 0.0 to 100 s
Fault current
Measurement range (mA)
Lower fault current (mA)
Upper fault current (mA)
4 - 20 NAMUR
3.8 - 20.5
3.5
22.6
4 - 20 US
4.0 - 20.8
3.75
22.6
Customized fail-safe mode
Last reliable value
Lower fault current
Upper fault current
Fail-safe value
Current value
Galvanic isolation All inputs and outputs are galvanically isolated PELV circuits with 60 V DC isolation from each
other and ground.
Maximum test voltage: 500 V AC
Cable Standard industrial signal cable with up to 3 twisted pairs with overall screen can be con‐
nected between the transmitter and the control system. Individual pair or overall screen is
optional depending on user requirements.
Voltage range Max. 24 V DC (active)
14 to 30 V DC (passive)
Technical data
11.5 Outputs
SITRANS FC330
198 Operating Instructions, 01/2019, A5E44030648-AB