Siemens SITRANS FC330 - Fraction: Sensor Dimension Dependent Default Settings (Process Values)

Siemens SITRANS FC330
280 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Sensor dimension m
3
/s m
3
/h
Low flow cut-off
DN 15 1.23333E-05 0.0444
DN 25 0.00005617 0.2022
DN 50 0.000140444 0.5056
DN 80 0.000368611 1.327
DN 100 0.000783333 2.82
DN 150 0.001269444 4.57
A.2.4 Fraction: Sensor dimension dependent default settings (Process values)
Fraction (if available)
Sensor dimension Unit Default value
Lower warning limit
DN 15 Mass flow kg/s -2.7777778
Volume flow m
3
/s
DN 25 Mass flow kg/s -12.152778
Volume flow m
3
/s
DN 50 Mass flow kg/s -31.25
Volume flow m
3
/s
DN 80 Mass flow kg/s -86.805556
Volume flow m
3
/s -0.641
DN 100 Mass flow kg/s -180.56
Volume flow m
3
/s -1
DN 150 Mass flow kg/s -298.61
Volume flow m
3
/s -2.3
Sensor dimension Unit Default value Range
Lower alarm limit
DN 15 Mass flow kg/s -8.84 -8.84 to +8.84
Volume flow m³/s -0.005 -0.005 to +0.005
DN 25 Mass flow kg/s -24.5 -24.5 to +24.5
Volume flow m³/s -0.015 -0.015 to +0.015
DN 50 Mass flow kg/s -98.2 -98.2 to +98.2
Volume flow m³/s -0.059 -0.059 to +0.059
DN 80 Mass flow kg/s -251 - 251 to +251
Volume flow m/s -0.249 -0.249 to +0.249
DN 100 Mass flow
Volume flow
Technical reference
A.2 Sensor dimension dependent default settings
SITRANS FC330
Operating Instructions, 01/2019, A5E44030648-AB 231