EasyManua.ls Logo

Siemens SITRANS FC330 - Page 232

Siemens SITRANS FC330
280 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Sensor dimension Unit Default value Range
DN 150 Mass flow
Volume flow
Sensor size Unit Default value
Upper warning limit
DN 15 Mass flow kg/s 2.7777778
Volume flow m
3
/s
DN 25 Mass flow kg/s 12.152778
Volume flow m
3
/s
DN 50 Mass flow kg/s 31.25
Volume flow m
3
/s
DN 80 Mass flow kg/s 86.805556
Volume flow m
3
/s 0.641
DN 100 Mass flow kg/s 180.56
Volume flow m
3
/s 1
DN 150 Mass flow kg/s 298.61
Volume flow m
3
/s 2.3
Sensor dimension Unit Default value Range
Upper alarm limit
DN 15 Mass flow kg/s 8.84 -8.84 to +8.84
Volume flow m
3
/s 0.005 -0.005 to +0.005
DN 25 Mass flow kg/s 24.5 -24.5 to +24.5
Volume flow m
3
/s 0.015 -0.015 to +0.015
DN 50 Mass flow kg/s 98.2 -98.2 to +98.2
Volume flow m
3
/s 0.059 -0.059 to +0.059
DN 80 Mass flow kg/s 251 - 251 to +251
Volume flow m
3
/s 0.249 -0.249 to +0.249
DN 100 Mass flow kg/s
Volume flow m
3
/s
DN 150 Mass flow kg/s
Volume flow m
3
/s
Sensor dimension Unit Range
Hysteresis
DN 15 Mass flow kg/s 0 to +8.84
Volume flow m
3
/s 0 to +0.005
DN 25 Mass flow kg/s 0 to +24.5
Volume flow m
3
/s 0 to +0.015
DN 50 Mass flow kg/s 0 to +98.2
Volume flow m
3
/s 0 to +0.059
Technical reference
A.2 Sensor dimension dependent default settings
SITRANS FC330
232 Operating Instructions, 01/2019, A5E44030648-AB

Table of Contents

Related product manuals