Bidirectional flow across zero with positive scaling
)&
v
v
mA
Kg/h
v
v
v
NJKNJK
P$
P$
P$
P$
① Lower scaling
② Low flow cut-off
③ Upper scaling
④ Maximum measurement value
⑤ Upper range
⑥ Lower range
⑦ Minimum measurement value
⑧ Lower alarm value
⑨ Measurement range
Current output setting
● Process value = Mass flow
● Direction = Bidirectional
● Current Mode = 4-20 mA US
● Upper Scaling = 400 kg/h
● Lower Scaling = -100 kg/h
● Fail Safe Mode = Minimum current
● Low Flow Cut-Off = 25 kg/h
Parameter assignment
8.2 Functions
SITRANS FC330
Operating Instructions, 01/2019, A5E44030648-AB 139