Characteristics of messages
The device provides two types of alarm formats, Siemens standard alarm classes and NAMUR
status signals, selected in Status icons.
The following tables summarize the two types of alarm formats in an overview.
The sequence of the symbols corresponds to the priority of the messages, beginning with the
most critical.
Siemens standard alarm classes
Icon Priority
level
Name Description
1 Maintenance failure
Maintenance alarm: maintenance demanded immediately
Measurement values are not valid
5 Maintenance warning
Maintenance warning
Measured signal still valid
6 Maintenance required
Maintenance required
Measured signal still valid
3 Process value alarm
Process value has reached an alarm limit
4 Process value warning
Process value has reached a warning limit
2 Function check
Change of configuration, local operation, or substitute value entered
Output signals are temporarily invalid
NAMUR status signals
Icon Priority
level
Name Description
1 Failure
Failure
Invalid output signal
3 Out of specification
Out of specification
Device will still work, but output signals may be invalid
4 Maintenance required
Maintenance request
Measured signal still valid
2 Function check
Function check
Output signal temporarily invalid
Diagnostics and troubleshooting
10.1 Device status symbols
SITRANS FC330
170 Operating Instructions, 01/2019, A5E44030648-AB