ID Icons Message Cause/Action
168 Totalizer 2 simulated Disable the simulation to return to normal operation.
169 Totalizer 3 simulated Disable the simulation to return to normal operation.
170 Loop current simulated Disable the simulation to return to normal operation.
172 Transmitter firmware in‐
compatible
The component does not have the expected firmware ver‐
sion. Update the product firmware or replace the compo‐
nent.
173 Sensor firmware incom‐
patible
The component does not have the expected firmware ver‐
sion. Update the product firmware or replace the compo‐
nent.
174 Firmware local operation
incompatible
The component does not have the expected firmware ver‐
sion. Update the product firmware or replace the compo‐
nent.
175 I/O firmware incompatible The component does not have the expected firmware ver‐
sion. Update the product firmware or replace the compo‐
nent.
177 Device startup Wait until the startup is finished. The startup time is speci‐
fied in the operating instructions. If the diagnostic persists
after the specified startup time, restart the device. If the
problem persists, contact Technical Support.
178 Transmitter firmware in‐
compatible
The component does not have the expected firmware ver‐
sion. Update the product firmware or replace the compo‐
nent.
Diagnostics and troubleshooting
10.2 Fault codes and corrective actions
SITRANS FC330
184 Operating Instructions, 01/2019, A5E44030648-AB