Y Loop current or flow
X Set measuring span
Example: Volume flow (linear)
For the volume flow measurement, you set the following values, for example:
Damping value: 2.0 s
Lower range value: 0.0 mbar
Upper range value: 0.6 bar
Application: Linear, square root (VSLN)
Unit: m
3
/h
Lower scaling point: 0.0 m
3
/h
Upper scaling point: 300 m
3
/h
Example: Mass flow (linear)
For the mass flow measurement, you set the following values, for example:
Damping value: 1 s
Lower range value: 0.0 mbar
Upper range value: 600 mbar
Application: Linear, square root (MSLN)
Unit: t/h
Lower scaling point: 0.0 t/h
Upper scaling point: 300 m
3
/ s
Parameter assignment
9.2 Parameter assignment over device with display
SITRANS P320/P420 (mA/HART)
Operating Instructions, 06/2018, A5E44852162-AA 113