3EDU
If the device is set for pressure measurement, no other measured variables (e.g. volume
flow) are available.
Example
For the pressure measurement, you set the following values, for example:
Damping value: 2.0 s
Lower range value: 0.0 bar
Upper range value: 5.0 bar
Application: Pressure: linear (PRESS)
Unit: bar
Lower scaling point: -
Upper scaling point: -
9.2.4.2 Level measurement
To set the application of the device for the level measurement, select the "level" characteristic
curve using the "Application" parameter (LEVEL).
For a level measurement, the device calculates the level height and the hydrostatic pressure.
The geometry of the vessel is not included in the calculation.
The device uses a linear characteristic curve:
Parameter assignment
9.2 Parameter assignment over device with display
SITRANS P320/P420 (mA/HART)
Operating Instructions, 06/2018, A5E44852162-AA 109