4.4.3.2 Measuring cell for gauge pressure, front-flush membrane
① Reference pressure opening ⑤ Filling liquid
② Measuring cell ⑥ Gauge pressure sensor
③ Process connection p
e
Inlet pressure
④ Seal diaphragm
Figure 4-8 Function chart of the measuring cell for gauge pressure, flush mounted diaphragm
The inlet pressure (p
e
) is transferred to the gauge pressure sensor ⑥ via the seal diaphragm
④ and the filling liquid ⑤, displacing its measuring diaphragm. The displacement changes
the resistance of the four piezoresistors (bridge circuit) of the gauge pressure sensor. The
change in the resistance causes a bridge output voltage proportional to the inlet pressure.
Pressure transmitters with measuring span ≤ 63 bar measure the inlet pressure against
atmosphere, those with measuring spans ≥ 160 bar the inlet pressure against vacuum.
4.4.3.3 Measuring cell for absolute pressure from the gauge pressure series
① Measuring cell ④ Filling liquid
② Process connection ⑤ Absolute pressure sensor
③ Seal diaphragm P
e
Inlet pressure
Figure 4-9 Function chart of measuring cell for absolute pressure
Description