9.2.29.2 Loop test with user defined loop current value
Procedure
1. Navigate into the parameter view.
Navigating in the views (Page 71)
2. In the parameter view, select the "Loop test" parameter [31].
3. Use the
button to confirm.
The loop test starts:
The "EDIT" symbol flashes.
The "Function check" symbol is displayed.
The "Co" symbol (constant current mode) is displayed.
4. Change to "USER" with the or button.
5. Use the button to confirm.
6. Set a value between 3.6 mA and 22.8 mA using the buttons or .
7. Use the button to confirm.
The loop test starts.
8. End the loop test with the button.
9.2.30 Start view [32]
Selects the value that is displayed as the first measured value in the measurement view.
For the selection to take effect, change from the parameter view to the measurement view or
restart the device.
Setting range: Edit view Measurement view
PRESS Pressure (P1)
STEMP Sensor temperature (P2)
ETEMP Electronics temperature (P3)
LEVEL Level (P4)
VOL Volume (P5)
VFLOW Volume flow (P6)
MFLOW Mass flow (P7)
USER Customized characteristic curve (P8)
% Percent of range (P9)
Parameter assignment
9.2 Parameter assignment over device with display
SITRANS P320/P420 (mA/HART)
138 Operating Instructions, 06/2018, A5E44852162-AA