Siemens SITRANS Series - 9.2.10 Upper fault current [12]; 9.2.11 Lower saturation limit [13]

Siemens SITRANS Series
260 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3.8 mA
22.8 mA20 mA
20.5 mA
4 mA3.55 mA
Normal operation
Lower fault current (factory setting)
Lower saturation limit (factory setting)
Upper saturation limit (factory setting)
Upper fault current (factory setting)
9.2.10 Upper fault current [12]
Adjusts the magnitude of the upper fault current .
Setting range: Between upper saturation limit und 22.8 mA
Factory setting: 22.8 mA, or as specified in order
3.8 mA
22.8 mA20 mA
20.5 mA
4 mA3.55 mA
Normal operation
Lower fault current (factory setting)
Lower saturation limit (factory setting)
Upper saturation limit (factory setting)
Upper fault current (factory setting)
9.2.11 Lower saturation limit [13]
Sets the lower threshold for the lower saturation limit.
The loop current cannot drop below the set threshold.
Setting range: Between lower fault current and 4 mA
Factory setting: 3.8 mA, or as specified in order
Parameter assignment
9.2 Parameter assignment over device with display
SITRANS P320/P420 (mA/HART)
Operating Instructions, 06/2018, A5E44852162-AA 121