The inlet pressure (p
e
) is transferred to the absolute pressure sensor via the seal
diaphragm and the fill fluid , displacing its measuring diaphragm.
The displacement changes the resistance of the four piezoresistors (bridge circuit) of the
absolute pressure sensor.
The change in the resistance causes a bridge output voltage proportional to the inlet
pressure.
4.4.3.4 Measuring cell for absolute pressure, front-flush membrane
S
H

Measuring cell Filling liquid
Process connection Absolute pressure sensor
Seal diaphragm p
e
Inlet pressure
Figure 4-10 Function chart of the measuring cell for absolute pressure, flush mounted diaphragm
The inlet pressure (p
e
) is transferred to the absolute pressure sensor via the seal
diaphragm and the filling liquid , and displaces its measuring diaphragm.
The displacement changes the resistance of the four piezoresistors (bridge circuit) of the
absolute pressure sensor.
The change in the resistance causes a bridge output voltage proportional to the inlet
pressure.
Description
4.4 Functional principle
SITRANS P320/P420 (mA/HART)
Operating Instructions, 06/2018, A5E44852162-AA 33