5.2.2 Installation (except level)
Mounting location
Verify that the mounting location meets the following conditions:
Accessible
Close to the measuring point
Vibration-free
Within the permitted ambient temperature values
Protect the pressure transmitter from:
Direct heat radiation
Rapid temperature fluctuations
Heavy contamination
Mechanical damage
Direct sunlight
Requirement
You have compared the desired operating data with the data on the nameplate.
You have adhered to the information on the remote seal during its installation.
Procedure
1. Attach the pressure transmitter to the process connection.
Use an appropriate tool (e.g. open-ended wrench with width across flats 36). Otherwise,
the measuring cell may be damaged.
2. Turn only on the key area above the process connection.
Caution: If you turn the pressure transmitter on the housing, the measuring cell may be
damaged.
3. To guarantee secure and vibration-free installation of the pressure transmitter, fasten it to
a mounting bracket (Page 45).
See also
Commissioning the device with display (Page 11)
Installing/mounting
5.2 Installation (except level)
SITRANS P320/P420 (mA/HART)
44 Operating Instructions, 06/2018, A5E44852162-AA