9.3 Parameter assignment over remote operation
9.3.1 Introduction
Introduction
This section describes the most important parameters and functions that are available
additionally over remote operation:
● "Quick Start" wizard
● Identification (TAG)
● Simulation
● Customized characteristic curve
● Sensor calibration
● Diagnostics functions
– Limit monitoring and event counter
– Trend log (not available on SITRANS P320)
9.3.2 Quick start
You use the "Quick start" wizard to configure your device in five steps for the required
application:
● Step 1: Identification
● Step 2: Application
● Step 3: Scaling
Note that you set the displayed pressure unit with the "Pressure units" (Page 102)
parameter and not with the wizard.
Set the unit of the selected application (e.g. volume, mass flow) also via the parameter
group "Settings > Current output > Scaling > Unit".
Step 4: Fault current
● Step 5: Summary
The summary provides an overview of the "old" and "new" parameters.
To store the parameters in SIMATIC PDM and transfer them to the device, click the "Apply"
button.
Parameter assignment
9.3 Parameter assignment over remote operation
SITRANS P320/P420 (mA/HART)
142 Operating Instructions, 06/2018, A5E44852162-AA