5. Open the shut-off valve at the pressure tapping point.
6. Open the shut-off valve for the process .
8.5.2 Differential pressure and volume flow
8.5.2.1 Commissioning in gaseous environments
Requirement
All shut-off valves are closed.
Procedure
Pressure transmitter above the differential pressure
transducer

Pressure transmitter below the differential pressure
transducer
Pressure transmitter Blowout valves
Stabilizing valve Condensate vessels (optional)
, Differential pressure valves Differential pressure transducer
Differential pressure lines 3-way valve manifold
Shut-off valves
To commission the pressure transmitter for gases, proceed as follows:
1. Open both the shut-off valves at the pressure tapping point.
2. Open the stabilizing valve .
Commissioning
8.5 Application examples
SITRANS P320/P420 (mA/HART)
Operating Instructions, 06/2018, A5E44852162-AA 91