EasyManua.ls Logo

Siemens SITRANS Series - 9.2.4.5 Set application; 9.2.5 Application point [06]

Siemens SITRANS Series
260 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Example
For the volume measurement, you set the following values, for example:
Damping value: 2.0 s
Lower range value: 0.0 mbar
Upper range value: 500.0 mbar
Application: Cylinder vessel (CYLIN)
Unit: m
3
Lower scaling point: 0.0 m
3
Upper scaling point: 10.0 m
3
9.2.4.5 Set application
Procedure
1. Navigate to the parameter view.
Navigating in the views (Page 71)
2. Select the "Application" parameter [05].
3. Select the parameter value.
Application [05] (Page 106)
Result
You have set the application of your device.
9.2.5 Application point [06]
Sets the application point from which scaling occurs according to the square root. Before the
application point, the scaling occurs in a linear relationship with the differential pressure.
This parameter is only visible when you have selected "Linear, square root" (VSLIN or MSLIN)
or "Hold at 0, square root" (VSOFF or MSOFF) using the "Application" parameter.
Setting range: 5 to 15%
Factory setting: 10%
See also
Volume and mass flow measurements (Page 111)
Parameter assignment
9.2 Parameter assignment over device with display
SITRANS P320/P420 (mA/HART)
Operating Instructions, 06/2018, A5E44852162-AA 115

Table of Contents

Other manuals for Siemens SITRANS Series

Related product manuals