3. Connect the wires to the connecting terminals "+" and "-".
Ensure the correct polarity!
4. Apply the shield to the screw of the ground terminal .
The screw of the ground terminal is electrically connected to the external protective
conductor connection.
NOTICE
Incorrect measured values with incorrect grounding
The device must not be grounded using the "+" connection. It may otherwise malfunction
and be permanently damaged.
If necessary, ground the device using the "-" connection.
6.2.3 Closing the device
Procedure
Cover over buttons Blanking plug
Cable gland Safety catch (front)
Safety catch (back) Cover (front), optionally with inspection window
Cover (rear) for electrical terminal compartment
Figure 6-3 View of the pressure transmitter: Left: Back right: Front view
1. Screw on the cover and as far as it will go.
Make sure that there is no gap between enclosure and cover.
2. Secure each cover with the cover catch and by removing the screw.
3. Close the cover over the buttons.