4.4.3.6 Measuring cell for differential pressure and flow rate

Inlet pressure P
+
Filling liquid
Pressure cap Seal diaphragm
O-ring Inlet pressure P
-
Measuring cell body Differential pressure sensor
Overload diaphragm
Figure 4-12 Function chart of the measuring cell for differential pressure and flow rate
Differential pressure is transmitted to the differential pressure sensor through the seal
diaphragms and the filling liquid .
When measuring limits are exceeded, the seal diaphragm is displaced until the seal
diaphragm rests on the measuring cell body . The differential pressure sensor is thus
protected against overloading since no further deflection of the overload diaphragm is
possible.
The seal diaphragm is displaced by the differential pressure. The displacement changes
the resistance of the four piezoresistors (bridge circuit) of the differential pressure sensor.
The change in the resistance causes a bridge output voltage proportional to the differential
pressure.
Description
4.4 Functional principle
SITRANS P320/P420 (mA/HART)
Operating Instructions, 06/2018, A5E44852162-AA 35