Between the measuring points, no
vacuum
H
2
7 m (23 ft), for halocarbon oil, however only H1
≤ 4 m(13.1 ft)
Start of scale value:
p
MA
= ρ
FL
* g * H
U
- ρ
oil
* g * H
V
Full scale value:
p
ME
= ρ
FL
* g * H
O
- ρ
oil
* g * H
V
Legend
p
MA
Start of scale value to be adjusted
p
ME
Full scale value to be adjusted
ρ
FL
Density of the measured medium in the container
ρ
oil
Density of the filling oil in the capillary line of the remote seal
g Local gravitational acceleration
H
U
Start of scale value
H
O
Full scale value
H
V
Gland distance
5.5 Removing
WARNING
Incorrect disassembly
The following risks may result from incorrect disassembly:
- Injury through electric shock
- Risk through emerging media when connected to the process
- Risk of explosion in hazardous area
In order to disassemble correctly, observe the following:
Before starting work, make sure that you have switched off all physical variables such as
pressure, temperature, electricity etc. or that they have a harmless value.
If the device contains hazardous media, it must be emptied prior to disassembly. Make
sure that no environmentally hazardous media are released.
Secure the remaining connections so that no damage can result if the process is started
unintentionally.
Installing/mounting
5.5 Removing
SITRANS P320/P420 (mA/HART)
54 Operating Instructions, 06/2018, A5E44852162-AA