Display
– NAMUR NE 107
NAMUR
– HCF
SIMATIC PDM/PLC
Symbol Device status Priority * Priority * Symbol Device status Priority *
Out of specifica‐
tion
4 3 Process value
alarm
8
Cause: Deviations from permissible ambient or process conditions detected by the device (by means of self-monitoring or
based on errors in the device) indicate that the measured value is unreliable or deviations from the set value in the actuators
is most likely greater than anticipated under normal operating conditions.
Process or ambient conditions will damage the device or result in unreliable output.
Measure: Check ambient temperature or process conditions. If possible, install device at different location.
Function test 2 2
(yellow)
Configuration
warning
9
Cause: Safety validation is not complete.
Measure: Acknowledge safety event in the Functional Safety menu and repeat safety commissioning.
Out of specifica‐
tion
4 3 Process value
warning
10
Cause: Deviations from permissible ambient or process conditions detected by the device (by means of self-monitoring or
based on warnings in the device) indicate that the measured value is unreliable or deviations from the set value in the
actuators is most likely greater than anticipated under normal operating conditions.
Process or ambient conditions can damage the device or result in unreliable output.
Measure: Check ambient temperature or process conditions. If possible, install device at different location.
No symbol is
displayed
Process value
tolerance
11
Cause:
Measure:
No symbol is
displayed
No symbol is
displayed
Configuration
changed
12
Cause:The device configuration has changed due to a work process.
Measure:
No symbol is
displayed
Good – OK No symbol is
displayed
No assignment 13
Cause:
Measure:
* The smallest number indicates the highest level of error severity.
** In SIMATIC PDM, the Siemens standard symbol as well as the corresponding NA\ symbol
is displayed (by the device display).
Diagnostics and troubleshooting
12.1 Device status symbols
SITRANS P320/P420 (mA/HART)
Operating Instructions, 06/2018, A5E44852162-AA 183