12.For the start of scale value 0 bar, check the zero point (4 mA).
If the differential pressure lines have equally high condensate columns with the same
temperature, the measurement result is error-free. Otherwise, repeat the zero-point
adjustment.
13.Close the stabilizing valve .
14.Fully open the differential pressure valves and .
Cleaning process cable
1. To clean the line, briefly open the drain valves .
2. Close the drain valve before vapor escapes.
Commissioning
8.5 Application examples
SITRANS P320/P420 (mA/HART)
96 Operating Instructions, 06/2018, A5E44852162-AA