20
Electronic Controller
Service Manual
SKOPE BME-N ActiveCore
29
Compressor cutting out.
The compressor cut out on its internal protection or
pressure switch.
2, 3, 4
Take a spare cartridge in case of refrigeration
system fault.
- Condenser blocked
- Poor installation / ventilation
- Cabinet seal leaking / door / cartridge
- Product; hot / blocking cabinet airflow
- Overloaded from excess door openings /
ambient
- Fan motor / blade (condenser / evaporator)
- Controller
- Compressor / gas leak = SWAP cartridge
30
Excessive automatic defrosting.
The system is automatically defrosting too frequently.
2, 3, 4
Take a spare cartridge in case of refrigeration
system fault.
- Door not self closing / gasket leaking
- Evaporator probe
- Evaporator motor / fan
- Controller
- Compressor / gas leak = SWAP cartridge
31
Compressor stalling.
The compressor is stalling on start up.
2, 3, 4
Take a spare cartridge in case of refrigeration
system fault.
- Condenser blocked
- Poor installation / ventilation
- Cabinet / cartridge gasket seals leaking
- Door not self closing / gasket leaking
- Product; hot / blocking cabinet airflow
- Overloaded from excess door openings /
ambient
- Fan motor / blade (condenser / evaporator)
- Controller
- Compressor / gas leak = SWAP cartridge
Table 4: Alarms (continued)
Code Description Service tech
type
Possible root cause