32
Replacement Procedures
Service Manual
SKOPE BME-N ActiveCore
Cartridge
Inter-
changeability
The SKOPE ActiveCore refrigeration cartridge is interchangeable between bottom and top
mount hydrocarbon (R290) ActiveCore fridges.
Top mount to bottom mount
When changing a cartridge from a top mount cabinet to a bottom mount cabinet, 2 bottom
plugs are required to seal the base of the cartridge. The plugs can be ordered in addition to
the refrigeration cartridge if required.
The plugs are included with new replacement cartridges.
Bottom mount to top mount
When changing from a bottom mount cabinet to a top mount cabinet, an evaporator lid, strap
brackets and hold down brackets must be fitted to seal the top of the evaporator tub, and to fix
the cartridge to the top of the cabinet. See the TME-N ActiveCore service manual (MAN80128
)
for more information.
4. Remove electrics cover and unplug the mains supply plug and cabinet plugs.
Note: The cartridge and electronic controller plugs do not need to be unplugged.
5. Pull the two cassette lifting levers forward to release, and rotate outwards to lower the refrigeration
cassette.
6. The refrigeration cartridge can now be pulled from the cabinet. Take care of the cables when
removing the cartridge.
7. When refitting the cartridge, ensure that:
• the gasket is in good condition.
• the electronic controller is refitted to the front kick panel.
• all plugs are securely reconnected.
• the electrics cover is refitted.
• the cartridge lifts up and seals correctly.
WARNING • Ensure no wires or plugs are trapped or damaged.
• Fully insert and lock all plugs. Pull the plugs to check.
• Refit and secure the electrics cover with screws
before reconnecting the mains power supply.
• Follow all applicable local regulations.
Procedure 25: To remove the refrigeration cartridge (continued)
WARNING
The hydrocarbon cartridge must only be used on a
hydrocarbon-compliant cabinet.