Error Cause and corrective measure
The transformer for internal
power supply does not sup-
ply voltage.
The transformer circuit breaker has tripped.
Corrective measures:
Ensure that the nominal current on the primary side of the transformer for internal
power supply is correctly set.
Switch the transformer circuit breaker back on.
The transformer for internal power supply is defective.
Corrective measures:
Replace the transformer for internal power supply. Contact the Service (see
Section17, page256).
The EMC filtering device is defective.
Corrective measures:
Replace the EMC filtering device. Contact the Service (see Section17, page256).
The cabling is damaged.
Corrective measures:
Ensure that the cabling is intact.
The lighting in the medium-
voltage compartment is not
working.
The lamps are defective.
Corrective measures:
Replace the lamps.
The circuit breaker has tripped.
Corrective measures:
Check whether apparent damage is visible in the corresponding electrical circuit.
If any damage is present, remove it.
Switch the circuit breaker back on.
The voltage supply of the MVPowerStation failed.
Corrective measures:
Ensure that the supply voltage is present (see error "Supply voltage is not
present").