- 24 -
5.3.1 Change of parameter block
To enable settings for all parameters.
Select “Basic” tab and change “PA19” value to “00E”.
Click the “PA19” row then click Selected Items Write”.
Cycle the power for parameters for this driver to be enabled.
Please click “Read".
When changing of each parameter, note the following points.
Note1) For Some of the parameters, there is "Enable once on again turning the power OFF after setting". (If
you do not cycle the power, it does not register the data in the driver.)
Note2) Selected Items Write: It writes the parameter values of the corresponding frame to the driver.
Single Axis Write: Writes all of the parameters to the driver.
Note3) Do not change “For manufacturer setting parameters. If you change by these by mistake, it may cause the
amplifier to not work properly.
5.3.2 Read of parameters
If you wish to read the parameters of the driver then, please select the Read operation.
From the View menu bar "parameter (A)" - please click on the "parameter setting (P)". "Parameter Settings"
screen will display.
Please click on the “Read".