EasyManua.ls Logo

SMC Networks LECSA Series - Point Table (Acceleration Time Constant;Deceleration Time Constant) Configuration; Other Settings

SMC Networks LECSA Series
96 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
- 61 -
5.7.5 Point Table (Acceleration time constant/Deceleration time constant) Configuration
< Acceleration time constant/Deceleration time constant Configuration>
Acceleration time constant (ms)/Deceleration time constant (ms) configuration:
Acceleration/deceleration (mm/s
2
) must be converted to the acceleration time constant/deceleration time constant (ms).
See below for the conversion formula.
Conversion example for a 8[mm] lead actuator driven at an acceleration of 3000 [mm/sec
2
]
Acceleration/Deceleration time constant (ms) = {3000 (r/min) ÷60 (S) } × 8 (mm) × 1000
3000 (mm/s
2
)
133 (ms)
The acceleration time constant/deceleration time constant defines the time in (ms) when the motor rotations of
(3000[/min]) are met.
The acceleration time constant/deceleration time constant must be a number between 0 and the allowable
acceleration/deceleration speed range for each actuator.
5.7.6 Other Settings
The dwell and auxiliary functions are set to 0 as default.
Do not change Manuf .1 (0) or Manuf .2 (0.00) from the initial values.
Acceleration time constant/deceleration time constant (ms) = {Rated rotation speed (r/min) ÷60 (S) } x screw lead (mm) x 1000
Acceleration/deceleration speed (mm/s
2
)
*As the scceleration time constant/deceleration time constant units are in ms; this is calculated as (s) ×1000
Rated Motor Rotation Speed (mm/s)
*Note)

Table of Contents