- 85 -
7.4 Positioning Mode (Point table method)
Positioning operation can be executed by setting the target position, rotation speed, acceleration time constant,
deceleration time constant to the point table data. (The maximum points that can be set in point table is 7.)
See “LECSA Operation Manual”,section 13.3 for details regarding the positioning mode (point table).
7.4.1 Operation Instruction of Point Table system
Select the point table No. represented by the values of DI0, DI1 and DI2. Start the operation by selecting ST1 or
ST2.
Point table No.
/Program No.
selection 1
<In point table method>
The point table No. and the home position return
mode are selected by DI0 to DI2.
<In program method>
The program No. is selected by DI0 to DI2.
Point table No.
/Program No.
selection 2
Home position return mode
Point table No.
/Program No.
selection 3
Turn PI1 on to resume the step stopped by the
SINK (1) command in the program.
If the parameter " PE01:Command mode selection " setting is "0000:Absolute value command system " .
Target position
[×10
STM
μm]
Acceleration
time constant
[ms]
Deceleration
time constant
[ms]
Note. Always set "0" or "2" to the auxiliary function in the last point table among the consecutive point tables.
0: When point table is used in absolute value command system
2: When point table is used in incremental value command system