- 57 -
5.7.3 Point table (Target position) Configuration
< Target position Configuration>
Please set the parameters as "PE02 (Feed function selection)" and "Feel length multiplication (STM) (Multiplier)".
Please change the "PE02 (Feed function selection)".
" Feel length multiplication (STM) (Multiplier)" will be automatically scaled.
For actuators with a stroke less than 1000mm, set parameter PE02 (Feed function selection) to 0000 and the
"Feed length multiplication (STM) (Multiplier)" value to x1.
For actuators with a stroke more than 1000mm, set parameter PE02 (Feed function selection) to 0001 and the
"Feed length multiplication (STM) (Multiplier)" value to x10.
Set the feed length multiplication (STM) (Multiplier) of target position in parameter No. PE02 (Feed function
selection).
Parameter No. PE02
setting
Feed length multiplication (STM) (Multiplier)
(Feed unit [μm])
Target position input range
[mm]
□□□0
1
-999.999 to +999.999
□□□1
10
-9999.99 to +9999.99
□□□2
100
-99999.9 to +99999.9
□□□3
1000
-999999 to +999999
Change of parameter [PE02(Feed function selection)].
1) Set the parameters of the PE02 in the "Positioning setting" tab.
2) Click on the "Single Axis Write" button.
3) Turn the power OFFand ON again. The Parameter is then enabled.
Change of the target position input range