ATySController C55/65 - 549866C - SOCOMEC
DENOMINATION TERMINAL DESCRIPTION CHARACTERISTICS
RECOMMENDED
CABLE SECTION
TIGHTENING
TORQUE
1
VOLTAGE SENSING
SOURCE 1
L1 / A Phase 1 / A 1Ph / 3Ph
50 - 332 / 575VAC
(50/60 Hz)
(+/- 10%)
Impulse V. Withstand Test: 6/8kV*
Ui 600V
0.75 - 2.5 mm²
AWG 18-14
0.5-0.6 N.m
4.4-5.3 lb.in
L2 / B Phase 2 / B
L3 / C Phase 3 / C
N Neutral
2
VOLTAGE SENSING
SOURCE 2
L1 / A Phase 1 / A
1Ph / 3Ph
50 - 332 / 575V
575VAC
(50/60 Hz)
(+/- 10%)
Impulse V. Withstand Test: 6/8kV*
Ui: 600V
L2 / B Phase 2 / B
L3 / C Phase 3 / C
N Neutral
3 RS 485
+ DATA + (A)
-
LiYCY sheilded
twisted pair
0.14 to 1,5 mm² /
AWG 30 - 14
0.22-0.25 N.m
4.4-5.3 lb.in
- DATA - (B)
NC Ground
4
CURRENT
TRANSFORMERS
I1 /Ia CT phase 1 / A
CT Input /1A or /5A
1.5-2.5 mm²
AWG 16-14
0.5-0.6 N.m
4.4-5.3 lb.in
I2 /Ib CT phase 2 / B
I3 /Ic CT phase 3 / C
In CT neutral
GND Ground
GND Ground
5
OPTIONAL AUX.
SUPPLY 24VDC
81 -
9-28VDC
24VDC -20%/+20%
for I/O modules
0.5-2.5 mm²
AWG 20-14
82 +
6
PROGRAMMABLE
INPUTS
70 COMMON
Do no connect to any power supply.
To be used with
dry contacts
Line maximum length100m
71 Input 1
72 Input 2
73 Input 3
74 Input 4
75 Input 5
76 Input 6
7
PROGRAMMABLE
OUTPUTS
11-12 NC/
11-14 NO
Output 1
Dry contacts
8A / 277 VAC 50/60 Hz
5A / 24 VDC
1.5-2.5 mm²
AWG 16-14
21-22 NC/
21-24 NO
Output 2
31-32 NC/
31-34 NO
Output 3
41-42 NC/
41-44 NO
Output 4
8 LATCHING RELAYS
51-52 NC/
51-54 NO
Output 5
61-62 NC/
61-64 NO
Output 6
9 CONFIG USB MicroUSB
USB 2.0 for
configuration
- MicroUSB Type B -
10 DIGIWARE BUS BUS
2x RJ45
DIGIWARE BUS
CAT V - 600V RJ45 UTP
RJ45 DIGIWARE
CABLE
-
Note:
- Use 7mm as stripping length for the controller terminals.
- Use 90°C copper wire for installations with ambient temperature from 35-60°C.
When the ambient temperature is above 60°C, Use 105°C copper wire.
* Impulse voltage withstand tests at 6kV between phases of the same source and 8kV between phases of a
different source.