55
EN
ATySController C55/65 - 549866C - SOCOMEC
14.1.3.3. LED CONFIG
This menu allows users to congure the X and Y LED (left side of the HMI) functioning mode, this is only available on the C65.
For C55 these LED are xed to the functions COM (LED active when switch is communicating) and Inhibit (LED is active when
inhibit, partial inhibit or total inhibit is activated).
The X and Y LEDs on the front face can be used for several purposes. For each one of them there are different
parameters that can be set:
FUNCTION: There are several functions that can be chosen:
- ALWAYS ON: LED permanently on.
- BUTTON RESPONSE: everytime a button is pressed it will become active (blink only).
- COM: communication report (active when communicating through RS485)
- SCHEDULER/EXERCISER ACTIVE: ON while the Engine Exerciser / Genset Scheduler is active (any of the
programs)
- INPUT REPORT: On when the selected input is active
- OUTPUT REPORT: On when the selected output is active
- NOT IN AUTO: On when the product is not in automatic mode (manual, inhibited, fault…)
- INHIBIT MODE: On when the controller has been inhibited
- LOAD SHED ACTIVE: On when load shedding (forced or smart) active
- GENSET COOLDOWN: On while cooldown timer is running (genset is cooling down before being turned off)
- LOAD CTRL: LOAD CONTROL output signal is active.
- TRANSF ONGOING: Transfer is taking place (it counts from detection/request of transfer to transfer nalized,
position reached)
- MAINTEN. ALARM: LED will be active when a maintenance alarm is ongoing.
- SERVICE: LED will be active when servicing is needed on the ATS system (based on the congured time between
inspection)
- None: LED not used
COLOR: Blue or Yellow.
BEHAVIOUR: Stable on (xed) or blinking.
REPORT TYPE: (only for FUNCTIONS Input Report or Output Report) will allow choosing between internal I/O or external
I/O modules (if any are connected).
REPORT IDX: Selects the input or output number to report.
- OPTIONS for the HMI buttons
TEST button use (between ON LOAD or OFF LOAD test)
LAMP TEST duration (s): This will alow the user to change the duration of the lamp test buton
available on the HMI. The
lamp test will start after the button is pressed and the user can end the lamp test at any time by pressing the button again
before this time limit.
POPUP DISPLAY : Users can select which pop-up windows to show, default and recommended value is "DISPLAY ALL"
which will show all pop-up indications. Other options are "HIDE ALARM" (will hide alarm pop-ups but will show timers),
"HIDE TIMER" (will hide timers but show alarms), "HIDE ALARM & TIMER (will hide both alarm and timer pop-ups.
- CHANGE PRODUCT NAME: allows changing the name of the ATS. This information will appear on all the dashboards and
menus on the top-right of the screen.
- SCREENSAVER TEXT: User can replace the default Socomec logo on the home screen by 4 lines of personalized text.
There are multiple options for size and police. before saving the conguration it is possible to preview the results.