Annex 16 - 4. Output list
These options can be congured in the "Parameters" > "I/O" > "INPUTS" menu:
TRIGRAM OUTPUT NAME DESCRIPTION C65 C55
PO1 POS 1 ORDER / CLOSE BRK1 Switch position order to go to Source 1 x x
PO2 POS 2 ORDER / CLOSE BRK2 Switch position order to go to Source 2 x x
PO0 POS 0 ORDER Switch position order to go to Position 0 (center off) x x
PA0 POS 0 ORDER S1 / OPEN BRK1 Switch position order to go to center-off (source 1) x x
PB0 POS 0 ORDER S2 / OPEN BRK2 Switch position order to go to center-off (source 2) x x
S1A S1 AVAILABLE
Source 1 available:
Output activated if source 1 is considered as available (see conditions of availa-
bility in the dedicated chapter of the manual).
x x
S2A S2 AVAILABLE
Source 2 available:
Output activated if source 2 is considered as available (see conditions of availa-
bility in the dedicated chapter of the manual).
x x
SCA ANY SOURCE AVAIL.
Source 1 OR source 2 available:
This output is activated when at least one source (S1 or S2) is available.
x x
S1U S1 UNAVAIL.
Source 1 unavailable:
Output activated if source 1 is not considered as available (see conditions of
availability in the dedicated chapter of the manual) or the source has been
inhibited.
x x
S2U S2 UNAVAIL.
Source 2 unavailable:
Output activated if source 2 is not considered as available (see conditions of
availability in the dedicated chapter of the manual) or the source has been
inhibited.
x x
AC1 S1 CLOSED
Source 1 closed:
This output has the function of an auxiliary contact. When the controller has the
input from the switch to be in source 1, the output will be active. This also consi-
ders the case where with no real information about the position, the controller
works in blind mode.
x x
AC2 S2 CLOSED
Source 2 closed:
This output has the function of an auxiliary contact. When the controller has the
input from the switch to be in source 2, the output will be active. This also consi-
ders the case where with no real information about the position, the controller
works in blind mode.
x x
AC0 OFF POSITION
Both sources open (center-off):
This output has the function of an auxiliary contact. When the controller has the
input from the switch to be in center-off, with both siwtches open, the output will
be active. This also considers the case where with no real information about the
position, the controller works in blind mode.
x x
LO1 S1 CLOSED + AVAIL
Load being supplied by source 1:
When actice, it indicates that source 1 is supplying the load and within the avai-
lability operating range. Source 1 has to reach the availability conditions.
x -
LO2 S2 CLOSED + AVAIL
Load being supplied by source 2:
When actice, it indicates that source 2 is supplying the load and within the avai-
lability operating range. Source 2 has to reach the availability conditions.
x -
LSC FORCED SHEDDING
Active when transfering to source 2 to load shed loads by connecting this
output to the open order on a circuit breaker or motorised switch. The function
Forced Load Shedding has to be active on the speic fucntions menu.
x -
FLT FAULTS ACTIVE At least 1 fault is active on the controller. Fault report x x
POP PROD. OPERATIONAL
Information abut the availability and correct functioning of the ATSE. The input
POP should be enabled and linked to the availability output of the RTSE.
x -
LCK PRODUCT LOCKED Report of padlocking of the product. x -
COP CTRL OPERATIONAL
Controller operational:
This output will be active while the controller is supplied, with no critical faults
active and with the required conditions to perform an automatic operation when
needed.
x -
TOS TEST ON LOAD This output is activated if a load test (thought the HMI) is ongoing. x -
EOS EXT TEST ON LOAD This output is activated if a load test (remote order) is ongoing. x -