61
EN
ATySController C55/65 - 549866C - SOCOMEC
14.1.6.3. Digiware
The product offers the option to choose between controlling external I/O modules through the RJ45 connectors (master) with
the Digiware bus or to be integrated into a complete Digiware system as a slave.
Control over I/O modules as a Digiware master.
IO-10C65 IO-10
IO-10C65C-31 I-30
IO-10C65C-31RS485M-70 I-30
IO-10C65
D-70
I-30
Controller as a slave, part of a Digiware chain, working as a U10 module that sends the voltage sensing information into the
chain to be read by other measurement modules.
IO-10C65C-31 I-30
IO-10C65C-31RS485M-70 I-30
IO-10C65
D-70
I-30
These two options can be selected on the menu, to change between slave and master, go to "PARAMETERS">"COMMUNIC
ATION">"DIGIWARE MODE".
Note: it’s not possible to be at the same time master over I/O and slave in the Digiware chain.
In slave mode the controller will not congure or control the I/O modules
14.1.6.4. Ethernet
For the ATyS C55/65 controller to be able to communicate on MODBUS TCP over Ethernet, it’s necessary to add a gateway
to convert from RS485 to RJ45 and use TCP protocol:
IO-10C65 IO-10
IO-10C65C-31 I-30
IO-10C65RS485M-70 I-30
When the D70 or M70 Socomec gateways are used, the ATyS CXX can be connected by RS485 or with the Digibus.