14.2.9. Tripping actions
This specic function allows user to congure how the controller should react if one or either of the breakers used in the RTSE trips.
Note: for these functions to be functional 2 inputs must be congured to "TRIP BRK1" and "TRIP BRK2".
Settings in the menu are the following:
SETTING OPTION DESCRIPTION
SWITCH BREAKER 1, BREAKER 2
Selects on which breaker the configuration
applies
TRIP ACTION
TRIP = SOURCE LOST, PARTIAL INHIBITION,
INHIBITION, TOTAL INHIBITION.
This setting defines the action to apply when
the trip signal for the corresponding breaker is
active. If "TRIP = SOURCE LOST" the controller
will define the source is unavailable and will
continue working automatically (will switch to
the opposite source if this is the active source).
In all other cases controller actions will be
inhibited (cf input menu for more details on the
types of inhibitions)
OP MODE AFTER TRIP
PREVIOUS MODE, AUTOMACTIC, PARTIAL
INHIBITION, INHIBITION
This setting allows user to select which
operating mode the controller will return to after
the trip signal has been disabled (input has
returned to inactive).
CHRG. TIME STATUS DISABLED, WHEN OPEN, WHEN CLOSED
Allows users to configure a charging time for
the breaker to give time to charge the spring
mechanism before sending an order. Users
can define if the spring is charged after a close
order or open order. If a charging time has been
configured the controller will wait the specified
duration before sending another order.
NB: each charging time will be overriden if an
input giving the charging status of the breaker
is configured.
CHARGING TIME(s) 0.00-15.00s
When a tripping action is detected ("TRIP BRK1 or "TRIP BRK2" is active) the controller will inform the user with a pop-up,
the information that the breaker is tripped, this information will also be visible on the main synoptic.
WARNING ! A tripping action on either one of breakers will be seen as "UNEXPECTED TRANSFER" .To
avoid having to reset the fault the trip action must be set to "TRIP = SOURCE LOST".
In any case the controller will register a tripping action in the log history as "UNEXPECTED TRANSFER".