9.6.1. Command circuits
LATCHING RELAY OUTPUTS (NC-NO-C)
INPUTS/ENTRÉES
OUTPUT RELAYS (NC-NO-C)
OUT 5OUT 6 OUT 4 OUT 3 OUT 2 OUT 1
12 14 1122 24 2132 34 3142 44 4152 54 5162 64 61
C IN6 IN5 IN4 IN3 IN2 IN1
70 76 75 74 73 72 7181 82
ATyS C65
Optional
Aux. Supply
24V (6W)
ATSE Controller
Config
USB
BATTERY
PILE
BR2032 LITHIUM
RS485
NC
MADE IN
FRANCE
L2 L3 NL1 L2 L3 NL1
ON
OFF
120Ω
IN I3 I2 I1
GND GND
CURRENT TRANSFORMERS : 1A or 5A
TRANSFORMATEURS DE COURANT : 1A ou 5A
SOURCE S2 SOURCE S1
By default, the inputs and outputs in the C55/65 are set up as follows:
BY DEFAULT CONFIGURATION CHANGES WHEN CHANGING RTSE TECHNOLOGY
INPUTS
ATYS R/D BREAKERS CONTACTORS ATYS FT ATYS DT
Input 1 SWITCH IN POS 1 BRK1 CLOSED SWITCH IN POS 1 SWITCH IN POS 1 SWITCH IN POS 1
Input 2 SWITCH IN POS 2 BRK2 CLOSED SWITCH IN POS 2 SWITCH IN POS 2 SWITCH IN POS 2
Input 3 SWITCH IN POS 0 BRK1 OPEN - - SWITCH S1 IN POS 0
Input 4 INHIBIT BRK2 OPEN - - SWITCH S2 IN POS 0
Input 5 MANUAL RETRANS
(1)
- - - -
Input 6 DOOR OPEN - - - -
OUTPUTS
Output 1 POS 1 ORDER CLOSE BRK1 POS 1 ORDER POS 1 ORDER POS 1 ORDER
Output 2 POS 2 ORDER CLOSE BRK2 POS 2 ORDER POS 2 ORDER POS 2 ORDER
Output 3 POS 0 ORDER OPEN BRK1 - - POS 0 ORDER S1
Output 4
FORCED SHEDDING (C65)
(1)
S1 AVAILABLE (C55)
OPEN BRK2 POS 0 ORDER S2
Output 5
LIFT (C65)
S2 AVAILABLE (C55)
- - - -
Output 6 GENSET START - - - -
Logic Impulse
(2)
Impulse Maintained Impulse Impulse
(1)
See chapter specic functions for more details.
(2)
Impulse duration and length and number of retries can be congured in "MAIN MENU" > "PARAMETERS" > "NETWORK" > "APPLICATION".