26
EN
ATySController C55/65 - 549866C - SOCOMEC
All inputs and outputs can be congured and functions can be changed by going in "MAIN MENU" > "PARAMETERS" > "I/O".
For the cabling, please consider the following table of functioning:
Cabling Output relays 1-4 Cabling Output Latching relays 5 & 6
Controller
cong STATE (relay)
OUT 1
12 14 11
Normally
Open (NO) (11-14)
OUT 1
12 14 11
Normally
Closed (NC) (11 - 12)
OUT 6
62 64 61
Normally
Open (NO) (61-64)
OUT 6
62 64 61
Normally
Closed (NC) (61-62)
Output
congured
as NO
OFF (not active) Open Closed Open Closed
ON (activated by rmware) Closed Open Closed Open
Controller not supplied Open Closed Closed* Open*
Output
congured
as NC
OFF (not active) Closed Open Closed Open
ON (activated by rmware) Open Closed Open Closed
Controller not supplied Open Closed Closed* Open*
* The ATyS C55/C65 include two bi-stable relays with backup energy, when the controller loses all sources of power supply (DPS, DC supply), the outputs
5 & 6 will activate using their independent backup power after the fail timer has timed out or 60s max from power failure detection. This is a safety
feature is designed to ensure power availability to the load in Main-Genset or Genset-Genset application by forcing generators to start in case of total
power loss.
It is highly recommended to congure the outputs 5 and 6 Normaly Open (NO) in order to benet from this function.