14.1.1. NETWORK parameters menu
The NETWORK menu allows the user with the Congurator prole to congure the installation parameters. Inside NETWORK,
there are 5 different submenus:
AUTODETECT. – When selected the function, a pop-up will show asking for a validation from the user to start autodetecting
the network type, the nominal voltage and frequency and the phase rotation. After the autodetection the result can be
consulted and modied in the SETUP menu. Information can be consulted on the SETUP menu.
SETUP – Settings concerning the installation can be congured here:
• NETWORK TYPE: number of poles and wires. See detail on page "Types of network" inside this chapter
• NOMINAL VOLTAGE
• NOMINAL FREQUENCY
• PHASE ROTATION (ABC or ACB // V1 V2 V3 or V1 V3 V2)
PHASE ROTATION CHECK: This can be enabled or disabled. By default it is enabled but it can be disabled for
applications where the user intentionally wants to do so. (Usually only for loads that are not affected by a change in
rotation).
VT USED: (“Used” or “Not used”) When voltage transformers are used for certain applications with V levels above
the maximum that the controller can measure directly (ph-ph: 576Vac). Example: 600/480V transformers for 600V
Networks. This ratio must be added to the next two lines in parameters “VT primary” and “VT secondary”.
WARNING ! In order to save the settings it’s mandatory to select SAVE CONFIG on the bottom of the screen
or press the "OK" button for 1.5s and a pop-up will appear asking for conrmation before “save & exit”.