EasyManua.ls Logo

socomec ATyS C55 - Page 99

socomec ATyS C55
110 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
99
EN
ATySController C55/65 - 549866C - SOCOMEC
OUTPUTS OUT 5-6
Output type latching / form C relay
Operating time <30ms
Contact type Volts free configurable NO/NC
Rating
AC1 8A 277Vac 50/60Hz
AC15 2A 277Vac 50/60Hz
DC1 5A 24Vdc
OUTPUTS OUT 1-4
Output type Non-Latching type
Operate time <30ms
Contact type Volts free configurable NO/NC
Rating
AC1 8A 277Vac 50/60Hz
AC15 2A 277Vac 50/60Hz
DC1 5A 24Vdc
RTC
Battery type Coin type cell (BR2032)
Battery voltage 3V
Battery lifetime (Average, depends on usage conditions) 6 years
RS485
Interface type 2 to 3 half duplex wires
Protocol MODBUS RTU
Baudrate programmable 1200-115200 bps
Function Configuration and data reading
Isolation Functional
Maximum distance
1200m @9600 baud
200m @115200 baud
Termination internal 120 ohms (selectable DIP switch)
DIGIWARE BUS (ONLY C65)
Function Connection between ATyS C65 and external modules
Cable type Specific cable with RJ45 connections
ENVIRONMENTAL SPECIFICATIONS
Ambient operating temperature -30º … +70ºC
Storage temperature -40º … +70ºC
Operating humidity 55ºC / 95% HR
Operating altitude <2000m
Vibrations IEC 60947-1
Shocks shocks according to Annexe Q IEC 60947-1
EMC classification Class A+B
INSULATION / OVERVOLTAGE CAT.
Impulse V withstand Uimp=4kV. Test = 8kV between sources/6kV between phases
Installation overvoltage category OVC III
Degree of pollution Pollution degree 3
USB
Connection USB 2
Type Type B Micro USB
Protocol Modbus RTU on USB