EasyManuals Logo

Studer NEXT3 User Manual

Studer NEXT3
133 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #118 background imageLoading...
Page #118 background image
Studer Innotec SA
next3
118 V 1.3 © Studer-Innotec SA next3 Tech manual
one attributed to deactivation will invert the hysteresis logic.
For example, the voltage battery pre-set could be configured with an Act_Th < Deact_Th to activate
a generator and charge the battery when the voltage is too low. The generator is then stopped
when the voltage corresponding to a charged battery is reached (Deact_Th).
The inverted hysteresis (Act_Th>Deact_Th) could be used for example to connect an additional load
when the voltage reaches a level of battery charged (Act_Th). This load is then disconnected if the
battery voltage reaches the Deact_Th level.
8.7.4.13 Additional info regarding Temporal Restriction
A temporal restriction can be applied to all the pre-sets mode expect “Scheduled time”. The
temporal restriction can be seen as an intermediate block between the signal of activation and the
relay coil. The following parameters can be set:
Activation Min Delay [sec]: Minimum delay before activation. The condition signal must be
high during all this period to activate the output.
Deactivation Min Delay [sec]: Minimum delay before deactivation. The condition signal must
be low during all this period to deactivate the output.
Activation Min Time [sec]: Minimum time during which the relay remains in activated position.
Deactivation Min Time [sec]: Minimum time during which the relay remains in deactivated
position.
Activation Max Time [sec]: Maximum time during which the relay remains in activated
position. To disable this parameter, enter the “-1” value.
Activation Hour Allowed 1&2 [sec]: Daily time range during which the relay activation is
allowed. The 2 daily hours are given in seconds starting from midnight.
Activation Weekdays Allowed: Weekdays allowing the relay to be activated. The different
days are represented in a bitfield format corresponding to:
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit 0
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Below an example of temporal restriction applied to a pre-set condition:
Parameters:
Activation Min. Delay
1 [sec]
Deactivation Min. Delay
2 [sec]
Activation Min. Time
4 [sec]
Deactivation Min. Time
4 [sec]
Activation Max. Time
15 [sec]
Activation Hour Allow1
12 :00

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Studer NEXT3 and is the answer not in the manual?

Studer NEXT3 Specifications

General IconGeneral
BrandStuder
ModelNEXT3
CategoryIndustrial Equipment
LanguageEnglish