EasyManua.ls Logo

Symmetricom TimeProvider 1000 - Setting the Input Frequency

Symmetricom TimeProvider 1000
216 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
097-58001-02 Revision C – August 2005 TimeProvider User’s Guide 101
Chapter 4 Provisioning the TimeProvider
Provisioning the Input Reference
Autonomous Message
TP-SSU 03-10-24 10:45:15
A 1179 REPT EVT
“GPS,EQPT:NA,FRMTYPE,NSA,03-10-24 10-45-15:\"GPS MODE HAS
CHANGED,AUTO\””
;
To manually set the location of the receiver, you must enter the latitude, the
longitude, and the altitude (in m) in the same command, using commas to separate
the parameters.
Sample Command
ED-EQPT::GPS:TS1000::POS=30-28-34.0N,97-50-16.0W,333.0;
Autonomous Message
TP-SSU 03-10-24 10:45:15
A 1179 REPT EVT
“GPS,EQPT:NA,FRMTYPE,NSA,03-10-24 10-45-15:\"GPS LOCATION
HAS CHANGED,MANUAL\””
;
Setting the Input Frequency
Use the ED-SYNC command to provision the input PRS frequency.
ED-SYNC:[<tid>]:<aid>:[<ctag>]::<keyword>=<value>;
This command has a default access level of ADMIN.
Sample Command
ED-SYNC::PRS:TS1000::FRMTYPE=5M;
Autonomous Message
TP-SSU 03-10-24 10:46:01
A 1179 REPT EVT
“PRS,EQPT:NA,FRMTYPE,NSA,03-10-24 10-46-01:\"INPUT
FRAMING TYPE HAS CHANGED,5M\””
;
<aid> <keyword> <value> Description Default value
PRS PRS input provisioning
FRMTYPE 1.544 M | 2M
(2.048 MHz) | 5M
| 6.312 M | 10M
Provisions the input
frequency of the PRS
input
2M

Table of Contents

Other manuals for Symmetricom TimeProvider 1000

Related product manuals