Chapter 4 Provisioning the TimeProvider
Provisioning Alarms
114 TimeProvider User’s Guide 097-58001-02 Revision C – August 2005
Provisioning Alarms
This section describes how you provision and manage alarms in the TimeProvider.
There are TL1 commands that allow you to:
îš„ Provision individual alarm levels
îš„ Provision system-wide alarm levels
îš„ Display current alarm settings
îš„ Display current alarms
îš„ Display alarm status
Alarms are displayed on the IMC LEDs; they also appear on the relay contact
closures on the Input module.
Provisioning the Alarm Levels
Use the SET-ATTR command to set the alarms associated with the IMC and IOC.
You can use this command to reset all alarm levels to the factory default values, and
to allow the TimeProvider to escalate alarms.
SET-ATTR:[<tid>]:<aid>:[<ctag>]::<keyword>[=<value>];
This command has a default access level of ADMIN.
<aid> <keyword> <value> Description
SYS System level
ELEVTIME ENABLE | DISABLE (default) Allow alarms to escalate from
Minor to Major and from
Major to Critical
FACTORY Set the alarm levels to factory
default values
<aid> <keyword> <value> Description
SYS
IMC
IOC
PRS
INPp (p = 1 | 2)
Alarm ID NR = Not Reported
NA = A non-alarm event
MN = Minor alarm
MJ = Major alarm
CR = Critical alarm
CLEAR = Clears an active
alarm; if the condition persists,
then the alarm is reissued
See the definitions for the
Alarm ID in the following table