097-58001-02 Revision C – August 2005 TimeProvider User’s Guide 115
Chapter 4 Provisioning the TimeProvider
Provisioning Alarms
Alarm ID
Description of Alarm
Condition
Possible
Alarm
Levels
Error
Delay
Default
Error
Delay
Editable?
Default Level
SSU
Mode
SUB
Mode
<aid> = SYS
COMPAT System components,
such as IOC software
and hardware are
incompatible
IMMED No MJ MJ
EXTALM1 External alarm
generated by external
equipment
NR | NA |
MN | MJ |
CR
IMMED No MN MN
EXTALM2 External alarm
generated by external
equipment
NR | NA |
MN | MJ |
CR
IMMED No CR CR
PWRA Loss of A power MN | MJ |
CR
IMMED No MJ MJ
PWRB Loss of B power MN | MJ |
CR
IMMED No MJ MJ
IOC1EQPT The IOC1 has been
physically inserted or
removed
IMMED No MJ MJ
IOC2EQPT The IOC2 has been
physically inserted or
removed
IMMED No MJ MJ
EXPNEQPT
The Expansion Panel
has been physically
inserted or removed
IMMED No MJ MJ
OUTA
EQPT
Output module in slot A
has been physically
inserted or removed
IMMED No MJ
OUTB
EQPT
Output module in slot B
has been physically
inserted or removed
IMMED No MJ
OUTC
EQPT
Output module in slot C
has been physically
inserted or removed
IMMED No MJ
OUTD
EQPT
Output module in slot D
has been physically
inserted or removed
IMMED No MJ

Table of Contents

Other manuals for Symmetricom TimeProvider 1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Symmetricom TimeProvider 1000 and is the answer not in the manual?

Symmetricom TimeProvider 1000 Specifications

General IconGeneral
BrandSymmetricom
ModelTimeProvider 1000
CategoryClock
LanguageEnglish

Related product manuals