Chapter 4 Provisioning the TimeProvider
Provisioning the Input Reference
110 TimeProvider User’s Guide 097-58001-02 Revision C – August 2005
Autonomous Message
TP-SSU 03-10-24 11:09:12
A 1189 REPT EVT
“GPS,EQPT:THRCHG,THRCHG,03-04-05 15-17-57,,,,:\”PM
THRESHOLD HAS CHANGED,MASK,GPS-R \””
;
Setting Alarm Levels for Performance Monitoring Faults
Once you set a threshold for performance monitoring faults, you can set the alarm
level to indicate that a fault has occurred. Use the SET-ATTR command to set the
alarm level.
SET-ATTR:[<tid>]:<aid>:[<ctag>]::<keyword>=<value>;
This command has a default access level of ADMIN.
Sample Command
SET-ATTR::GPS:TS1000::MTIE=MJ;
This command sets the GPS input to report a Major alarm when the MTIE
performance threshold is exceeded.
Autonomous Message
TP-SSU 03-05-15 09:59:09
A 1189 REPT EVT
“GPS,EQPT:ALMCHG,ALMCHG,03-04-05 15-17-57,,,,:\”ALARM
PARAMETER HAS CHANGED,GPS,MJ\””
;
<aid> <keyword> <value> Description
GPS, PRS,
INP1, INP2
Input
MTIE NR | NA | MN | MJ | CR The alarm level when the specified
input has exceeded at least one of
the MTIE thresholds
FFOFF NR | NA | MN | MJ | CR The alarm level when the specified
input has exceeded the FFOFF
threshold

Table of Contents

Other manuals for Symmetricom TimeProvider 1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Symmetricom TimeProvider 1000 and is the answer not in the manual?

Symmetricom TimeProvider 1000 Specifications

General IconGeneral
BrandSymmetricom
ModelTimeProvider 1000
CategoryClock
LanguageEnglish

Related product manuals