48
83507013 Rev G
Notes:
1. If the power supply is operating in remote sense and either the positive or negative
load wire is not connected, an internal protection circuit will activate and shut down
the power supply. To resume operation, turn the AC On/Off to the Off position,
connect the open load wire, and turn On the power supply.
2. If the power supply is operated without the remote sense lines or local sense
jumpers, it will continue to work, but, the output voltage regulation will be degraded.
Also, the OVP circuit may activate and shut down the power supply.
3.10.4 J2 sense connector technical information
J2 connector type: MC 1.5/5-G-3.81, Phoenix.
Plug type: MC 1.5/5-ST-3.81, Phoenix.
Wire AWG; 28 up to 16.
Stripping length: 7mm (0.28 inches).
Tightening torque: 0.22-0.25Nm (1.95-2.21Lb-Inch.).
3.11 Repackaging for Shipment
To ensure safe transportation of the instrument, contact the TDK-Lambda Americas Inc.
sales or service facility near you for Return Authorization and shipping information. Please
attach a tag to the power supply describing the problem and specifying the owner, model
number and serial number of the power supply. Refer to Warranty Information for further
instructions.