5-54              
5-5 Gain Adjustment 
z  The Servo controller provides 3 control loops as diagram shown below. 
z  Control methods are: Current Control, Speed Control and Position Control. 
 
Current 
Controllor
Power 
Circuit
SM
Speed 
Controllor
PG
Position 
Controllor
Host 
Controllor
 
z  Diagram above shows the three control loops. 
z  Current (Inner loop), Speed (middle loop) and position (outer loop). 
z  Theoretically, the bandwidth of inner control loop must be higher than the bandwidth of  
the outer control loop, otherwise the whole control system will become unstable, and 
cause vibration or abnormal response. 
z  The relationship between the band width for these three control loops is as follows: 
Current Loop (Inner) >Speed Loop (Middle )>Position Loop (outer). 
z  The default current control bandwidth has already been set for optimum response; so 
Only speed and position control loop gains may be adjusted. 
z  Table below shows the Gain adjustment parameters for the three control loops. 
 
Parameter  Name  Default  Unit  Setting Range 
Control 
Mode 
Sn211  Speed Loop Gain 1  40  Hz  10~1500  Pe/Pi/S 
Sn212 
Speed Loop Integration Time 
Constant 1 
100 
x0.2 
msec 
1~5000 Pe/Pi/S 
Sn213  Speed Loop Gain 2  40  Hz  10~1500  Pe/Pi/S 
Sn214 
Speed Loop Integration Time 
Constant 2 
100 
x0.2 
msec 
1~5000 Pe/Pi/S 
Pn310  Position Loop Gain 1  40  1/s  1~1000  Pe/Pi 
Pn311  Position Loop Gain 2  40  1/s  1~1000  Pe/Pi 
Pn312 
Position Loop Feed-Forward 
Gain  
0 %  0~100  Pe/Pi 
Cn025  Load Inertia Ratio   10  x0.1  0~1000  Pe/Pi/S