7-1-3 Modbus communication protocol for RS-485 
z  The MODBUS protocol allows an easy communication within types of network 
architectures,before start to communication with slave device, set the ID number 
( Cn036 ) for Servo drive respectively, server distinguish ID number for controlling 
specific client station.   
z  Standard Modbus networks combine two transmission modes: ASCII or RTU: 
ASCII(American Standard Code for information interchange) Mode and RTU (Remote 
Terminal Unit) Mode, Use Cn038 to select ASCII or RTU mode. 
 
Coding method 
ASCII Mode 
8-bits Data consist of two ASCII code. 
          Ex: Data 26H 1-byte , the ’26’ convert to ASCII code is include character ’2‘ Æ <32H> and ’6’ 
Æ<36H> 
ASCII Chart    ( 0 ~ 9    and    A ~ F ): 
Character ‘0’ ‘1’ ‘2’ ‘3’ ‘4’ ‘5’ ‘6’ ‘7’ 
ASCII 
code(Hex) 
30H  31H  32H  33H  34H  35H  36H  37H 
Character ‘8’ ‘9’ ‘A’ ‘B’ ‘C’ ‘D’ ‘E’ ‘F’ 
ASCII 
code(Hex) 
38H  39H  41H  42H  43H  44H  45H  46H 
 
RTU Mode 
  Each 8bits is consist of 2 Hex number (4-bits per Hex number). 
          Ex.: Data 26H, the data length is 1-byte.